Текущее местоположение: первая страница>>Products>>Intelligent Switch

Products

Current-Limiting Fire Alarm Protector FHXL-63

FHXL-63 series is the current-limiting fire alarm protector, and it is a comprehensive protector with multiple protection functions for overvoltage, undervoltage, overcurrent, leakage, temperature and smoke detection. The product has the advantages of modularization, intelligence, visualization and so on. At the same time, it supports the standard Modbus485 communication protocol. All protection parameters such as overvoltage, undervoltage and overcurrent protection can be set according to the power demand, so as to ensure that the protector can instantly cut off the power supply when overvoltage, undervoltage, overcurrent and other faults occur in the line, and the electrical equipment can be protected from damage.
Техническая документация Онлайн консультация

I. Introduction

FHXL-63 series is the current-limiting fire alarm protector, and it is a comprehensive protector with multiple protection functions for overvoltage, undervoltage, overcurrent, leakage, temperature and smoke detection. The product has the advantages of modularization, intelligence, visualization and so on. At the same time, it supports the standard Modbus485 communication protocol. All protection parameters such as overvoltage, undervoltage and overcurrent protection can be set according to the power demand, so as to ensure that the protector can instantly cut off the power supply when overvoltage, undervoltage, overcurrent and other faults occur in the line, and the electrical equipment can be protected from damage.

The product has compact structure, beautiful appearance, and there is standard guide rail for installation.

II. Working conditions and current protection parameters

1. In case of the first normal power-on, the device automatically closes after 1s delay; and when powered on for the first time, under the conditions of overvoltage, undervoltage, overcurrent and leakage, the device will automatically open within 3 seconds;

2. When powered on for the first time, the smoke sensor needs to be heated for 60 seconds, and then the product enters the protection state. After smoke alarm occurs and the fault is removed, it is necessary to manually press the Reset key for 2 seconds, then the smoke alarm can be released.

3. Current protection parameters:

a. ≥ 1.05 times current, < 3 minutes opening.

b. ≥ 1.2 times current, setting range 1 to 120 seconds, 10 seconds by default

c. ≥ 2 times current, ≤0.2 second opening.

4. The ambient temperature shall not exceed + 40°C, it shall not be lower than-5°C; and the average temperature within 24 hours shall not exceed + 35°C; at + 40°C, the ambient air humidity shall not exceed 50%.

5. The altitude of the installation site shall not exceed 2000 meters.

6. Pollution level: III.

7. In the installation environment, there shall be no explosive dangerous medium, no corrosive and destructive gas and conductive dust, and no invasion of rain and snow.

III. Functions of the keys

1. Setting key: Press and hold the Setting key for 2 seconds, it enters the setting state. After entering the setting state, every time you press the key, the system will enter the next setting menu;

2. Shift key: query the current real-time operation parameters of the product. In the setting state, it has the digit shift function;

3. Data key: query the last fault information of the product and change the parameters to be set under the setting state;

4. Reset key: When the first overcurrent or leakage occurs, the product will automatically switch on after delaying the specified reset time. When the second overcurrent, leakage or fire alarm occurs, it must be confirmed that there is no fault in the circuit, then you need to manually press the Reset key to make the product switch on, and press the Reset key for 2 seconds to save and exit the setting state.

Current-limiting fire protector.jpg

Ключевые моменты для выбора

продукт:Current-Limiting Fire Alarm Protector FHXL-63

Введение:FHXL-63 series is the current-limiting fire alarm protector, and it is a comprehensive protector with multiple protection functions for overvoltage, undervoltage, overcurrent, leakage, temperature and smoke detection. The product has the advantages of modularization, intelligence, visualization and so on. At the same time, it supports the standard Modbus485 communication protocol. All protection parameters such as overvoltage, undervoltage and overcurrent protection can be set according to the power demand, so as to ensure that the protector can instantly cut off the power supply when overvoltage, undervoltage, overcurrent and other faults occur in the line, and the electrical equipment can be protected from damage.

Ключевые примечания

брендELEJG / Вэньчжоуская компания Jiangguang Electric Technology Co., Ltd.
Название моделиCurrent-Limiting Fire Alarm Protector FHXL-63
Техническая документацияПосмотреть/скачать инструкцию
Вход на консультациюСвязаться с нами

Часто задаваемые вопросы

Q:Current-Limiting Fire Alarm Protector FHXL-63 Для каких сценариев подходит?
A: Подходит для сценариев распределения и энергопотребления, требующих электрической защиты, ограничения тока, защиты от повышенного и пониженного напряжения или защиты от дугового замыкания. ; Подробную информацию см. в описании на этой странице и в параметрах в руководстве.
Q: Как получить точные параметры и способы подключения?
A: Откройте «Техническую документацию» на этой странице или перейдите в раздел «Техническая поддержка и часто задаваемые вопросы», чтобы ознакомиться с ней. Техническая поддержка · Часто задаваемые вопросы
Q: Как связаться с производителем для подтверждения выбора?
A: Вы можете нажать «Онлайн-консультация» на этой странице, чтобы начать разговор с умным помощником AI, или связаться с нами. ; Пожалуйста, укажите рабочее напряжение, ток и требования к защите. Связаться с нами
Оставить сообщение онлайн

鲁ICP备2021012790号-1